Staff Answer
Sep 30, 2026 - 10:03 AM
For the EnerSys PowerSafe SBS 190F (the 12V front-terminal TPPL telecom battery), the manufacturer's float spec is:
- 2.27–2.29 volts per cell at 68°F (20°C) → 13.62–13.74V for the 12V battery
- 2.25–2.27 volts per cell at 77°F (25°C) → 13.50–13.62V for the 12V battery
Practical target: ~13.65V at 68°F / ~13.5V at 77°F. If the charger does temperature compensation, EnerSys says never to let the compensated setting drop below 2.21 VPC (13.26V). They also note float should be a constant-voltage charge and applied within seven days after any discharge.
Because it's thin plate pure lead rather than standard AGM, it floats a bit lower than the generic 13.8V many chargers default to — a plain "AGM" preset at 13.8V+ will slowly overcharge it, so use a charger that can hold ~13.5–13.65V.
High-Tech Battery Solutions Inc